G7SA

Özellikler

Soket veya PCB montajı için G7SA Zorlamalı açmalı röleler

Zorlamalı kontaklı ince G7SA röle ailesi dört veya altı kutuplu olarak çeşitli kontak kombinasyonlarında mevcuttur ve güçlendirilmiş yalıtım sağlamaktadır. Terminaller kolay PCB yerleşimi için düzenlenmiştir. Doğrudan bir PCB' ye lehimlenebilir veya P7SA soketlerle kullanılabilir. 

  • Zorlamalı kontaklar
  • EN 50205'ye uygundur
  • 6A 240VAC ve dirençli yükler için 6A 24VDC
  • Girişler, çıkışlar ve kutuplar arasında güçlendirilmiş yalıtım
  • 4- ve 6-kutuplu röleler mevcuttur
Özellikler ve sipariş bilgisi

Ordering information

Relays with forcibly guided contacts

Type

Sealing

Poles

Contacts

Rated voltage

Order code

Standard

Flux-tight

4 poles

3PST-NO, SPST-NC

24 VDC1

G7SA-3A1B

DPST-NO, DPST-NC

G7SA-2A2B

6 poles

5PST-NO, SPST-NC

G7SA-5A1B

4PST-NO, DPST-NC

G7SA-4A2B

3PST-NO, 3PST-NC

G7SA-3A3B

Sockets

Mounting

Terminal type

LED indicator

Poles

Coil rated voltage

Order code

Front-
mounting

Push-In Plus terminals

Yes

4 poles

24 VDC

P7SA-10F-ND-PU

6 poles

P7SA-14F-ND-PU

Screw terminals

Yes

4 poles

P7SA-10F-ND

6 poles

P7SA-14F-ND

No

4 poles

P7SA-10F

6 poles

P7SA-14F

Back-
mounting

PCB terminals

No

4 poles

P7SA-10P

6 poles

P7SA-14P

Specifications

Coil

Rated voltage

Rated current

Coil resistance

Must-operate voltage

Must-release voltage

Max. voltage

Power consumption

24 VDC

4 poles: 15 mA

6 poles: 20.8 mA

4 poles: 1,600 Ω
6 poles: 1,152 Ω

75% max. (V)

10% min. (V)

110% (V)

4 poles: Approx. 360 mW
6 poles: Approx. 500 mW

Note: Refer to datasheet for details

Contacts

Load

Resistive load (cos φ = 1)

Rated load

6 A at 250 VAC, 6 A at 30 VDC

Rated carry current

6 A

Max. switching voltage

250 VAC, 125 VDC

Max. switching current

6 A

Max. switching capacity (reference value)

1,500 VA, 180 W

Relays with forcibly guided contacts

Contact resistance

100 mΩ max. (The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.)

Operating time 2

20 ms max.

Response time 1

10 ms max.
(The response time is the time it takes for the normally open contacts to open after the coil voltage is turned OFF.)

Release time 1

20 ms max.

Insulation resistance

100 MΩ min. (at 500 VDC) (The insulation resistance was measured with a 500 VDC megger at the same places that the dielectric strength was
measured.)

Dielectric strength 3 4

Between coil contacts/different poles: 4,000 VAC, 50/60 Hz for 1 min
(2,500 VAC between poles 3-4 in 4-pole Relays or poles 3-5, 4-6, and 5-6 in 6-pole Relays.)

Between contacts of same polarity: 1,500 VAC, 50/60 Hz for 1 min

Durability

Mechanical

10,000,000 operations min. (at approx. 36,000 operations/hr)

Electrical

100,000 operations min. (at the rated load and approx. 1,800 operations/hr)

Min. permissible load5

5 VDC, 1 mA (reference value)

Ambient temperature 6

Operating: −40 to 85°C (with no icing or condensation)

Ambient humidity

Operating: 35 to 85%

Approved standards

EN61810-1 (IEC61810-1), EN50205, UL508, CSA22.2 No. 14

Note: The values listed above are initial values.

 

Please check Omron in the Internet for updated information on product reliability data and the SISTEMA libraries: http://industrial.omron.eu/safety


1. 12 VDC, 21 VDC, 48 VDC are available on request.
2. These times were measured at the rated voltage and an ambient temperature of 23°C. Contact bounce time is not included.
3. Pole 3 refers to terminals 31-32 or 33-34, pole 4 refers to terminals 43-44, pole 5 refers to terminals 53-54, and pole 6 refers to terminals 63-64.
4. When using a P7SA socket, the dielectric strength between coil contacts/different poles is 2,500 VAC, 50/60 Hz for 1 min.
5. Min. permissible load is for a switching frequency of 300 operations/min.
6. When operating at a temperature between 70°C and 85°C, reduce the rated carry current (6 A at 70°C or less) by 0.1 A for each degree above 70°C.
1. 12 VDC, 21 VDC, 48 VDC are available on request.
2. These times were measured at the rated voltage and an ambient temperature of 23°C. Contact bounce time is not included.
3. Pole 3 refers to terminals 31-32 or 33-34, pole 4 refers to terminals 43-44, pole 5 refers to terminals 53-54, and pole 6 refers to terminals 63-64.
4. When using a P7SA socket, the dielectric strength between coil contacts/different poles is 2,500 VAC, 50/60 Hz for 1 min.
5. Min. permissible load is for a switching frequency of 300 operations/min.
6. When operating at a temperature between 70°C and 85°C, reduce the rated carry current (6 A at 70°C or less) by 0.1 A for each degree above 70°C.

Sorunuz mu var?

Yardımcı olmaya hazırız.

Bize ulaşın

Ürün güncellemelerine abone olun

Ürün yenilikleri, çözümler ve hizmetleri hakkındaki bültenlere doğrudan gelen kutunuzdan erişin.

Omron’ un e-bültenine abone olduğunuz için teşekkür ederiz. Kısa bir süre içerisinde bizden bir e-posta alacaksınız. Bu e-posta, bülten aboneliğinizi etkileştiren bir bağlantı içermektedir. Bu metot hukuki konular nedeniyle ve kimsenin e-posta adresinizi kötüye kullanmadığından emin olabilmek için kullanılmaktadır.

Teknik zorluklar yaşamaktayız. Form gönderme işleminiz başarılı olmadı. Lütfen özürlerimizi kabul edin ve daha sonra tekrar deneyin. Detaylar: [details]

Download

Ürün dokümanları

Veri sayfaları, kılavuzlar ve broşürleri indirin.

İndirme merkezine göz atın

Eğitim kursları

En iyi mühendislerimizden eğitim alın. Başlangıç seviyesinden gelişmiş seviyeye.

Eğitim kurslarını görüntüleyin